The reasons and solutions of the plate of plate heat exchanger board misplaced
During the use of the plate heat exchanger, it is inevitable that the plates of the plate heat exchanger will be misaligned. After the plates are misaligned, leakage or leakage will occur quickly, which must be handled in time to ensure the normal operation of the heat exchange equipment. If you want to solve the problem of plate dislocation of heat exchanger, you should first understand the reason of plate dislocation of plate heat exchanger.
reason
(1) In the process of long-term use, multi-pass combination, and the flow and pressure of the medium in the heat exchanger also vary greatly. When the heat exchanger cannot withstand this pressure, the plate of the plate heat exchanger will be dislocated.
(2) The sealing gasket of the plate heat exchanger slides away from the gasket groove, and the plate dislocation will also occur.
resolvent
(1) The on-site maintenance personnel can first draw out the damaged plates and the leaking plates in pairs (A+B). If the number of dislocated plates is small and the number of reduced flow channels is small, the equipment can continue to be used after assembly, and the impact on production is not great. This solution is applicable to the situation that there are no replaceable new plates on site and the equipment cannot be stopped. If conditions permit, it is better to stop the machine for replacement and maintenance.
(2) When the sealing gasket of the plate heat exchanger slides away from the gasket groove, it is necessary to replace the deformed plate and the gasket that slides away from the gasket groove in time when dealing with this dislocation.